Thursday, March 4, 2010

ES-5000 Energy Server

ES-5000 Energy Server

 
 
Technical Highlights
Inputs
Fuels Natural Gas, Directed Biogas
Input fuel pressure 15 psig
Fuel required @ rated power 0.661 MMBtu/hr of natural gas
Water required (for startup only) 120 gallons municipal water
Outputs
Rated power output (AC) 100 kW
Electrical efficiency (LHV net AC) > 50%
Electrical connection 480V @ 60 Hz, 4-wire 3 phase
Physical
Weight 10 tons
Size 224" x 84" x 81"
Emissions
NOx < 0.07 lbs/MW-hr
SOx negligible
CO < 0.10 lbs/MW-hr
VOCs < 0.02 lbs/MW-hr
CO2 @ specified efficiency 773 lbs/MW-hr on natural gas,
carbon neutral on Directed Biogas
Environment
Standard temperature range 0° to 40° C (extreme weather kit available)
Max altitude at rated power 6,000 ft. MSL
Humidity 20% - 95%
Seismic Vibration IBC 2003: Site Class D
Location Outdoor
Noise @ rated power < 70 DB @ 6 feet
Codes and Standards
Complies with Rule 21 interconnection standards
Exempt from CA Air District permitting; meets stringent CARB 2007 emissions standards
Product Listed by Underwriters Laboratories Inc. (UL) to ANSI/CSA America FC 1
Additional Notes
Operates in a grid parallel configuration
Includes a secure website for you to showcase performance & environmental benefits
Remotely managed and monitored by Bloom Energy
Capable of emergency stop based on input from your facility